Configuring the EtherNet/IP Module
4-7
Step 3.
Reset the module. Refer to Resetting the Module in
section 4.7.2.
The Net A status indicator will be solid green or flashing green if the
IP address is correctly configured.
To set a subnet mask using parameters:
Step 1.
Verify that module parameter 2 (BOOTP) is set to
Disabled. This parameter must be set to Disabled to
configure the subnet mask using parameters.
Step 2.
Set the value of module parameters 7 through 10 (Subnet
Cfg 1 through Subnet Cfg 4) to the desired value for the
subnet mask as shown in figure 4.6.
Step 3.
Reset the module. Refer to Resetting the Module in
section 4.7.2.
To set a gateway address for the module using parameters
Step 1.
Verify that module parameter 2 (BOOTP) is set to
Disabled. This parameter must be set to Disabled to
configure the gateway address using parameters.
Step 2.
Set the value of module parameters 11 through 14
(Gateway Cfg 1 through Gateway Cfg 4) to the IP address
of the gateway device as shown in figure 4.7.
Step 3.
Reset the module. Refer to Resetting the Module in
section 4.7.2.
Figure 4.6 Sample Subnet Mask Screen on an LCD OIM
Figure 4.7 – Sample Gateway Screen on an LCD OIM
Port 5 Device
MDCOMM-ENET
Parameter #: 07
Subnet Cfg 1
0
0 <> 255
Default = 0.0.0.0
255. 255. 255. 255
[Subnet Cfg 1]
[Subnet Cfg 2]
[Subnet Cfg 3]
[Subnet Cfg 4]
Port 5 Device
MDCOMM-ENET
Parameter #: 11
Gateway Cfg 1
0
0 <> 255
Default = 0.0.0.0
255. 255. 255. 255
[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]