beautypg.com

Rockwell Automation MD65 EtherNet/IP Communication Module User Manual

Page 156

background image

C-28

EtherNet/IP Communications Module

Instance Attributes

Services

6

Get

Number of
Recorded Faults

WORD

Number of faults/events in the
queue. A “0” indicates the fault
queue is empty.

7

Get

Fault Parameter
Reference

WORD

Reserved

Attribute

ID

Access

Rule

Name

Data Type

Description

Attribute

ID

Access

Rule

Name

Data Type

Description

0

Get

Full/All
Information

STRUCT of WORD
STRUCT of
BYTE
BYTE
STRING[16]
STRUCT of
LWORD

BOOL[16]

WORD
CONTAINER[n]

Fault code
Fault source
MDI port
MDI Device Object
Fault text
Fault time stamp
Timer value (0 = Timer not
supported)
BOOL[0]: (0 = invalid data,

1 = valid data)

BOOL[1]: (0 = elapsed time,

1 = real time)

BOOL[2 - 15]: Not used
Reserved
Reserved

1

Get

Basic
Information

STRUCT of WORD
STRUCT of
BYTE
BYTE
STRUCT of
LWORD

BOOL[16]

Fault code
Fault source
MDI port
MDI Device Object
Fault time stamp
Timer value (0 = Timer not
supported)
BOOL[0]: (0 = invalid data,

1 = valid data)

BOOL[1]: (0 = elapsed time,

1 = real time)

BOOL[2 - 15]: Not used

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

Yes

Yes

Set_Attribute_Single