![background image](/manuals/581228/134/background.png)
C-6
EtherNet/IP Communications Module
Class Attributes
23
Logic Command for Drive 1
Out
16
24
Feedback for Drive 1
In
16
25
Reference for Drive 1
Out
16
26
Feedback for Drive 1
In
16
27
Logic Command Status for Drive 2
Out
16
28
Logic Status for Drive 2
In
16
29
Reference for Drive 2
Out
16
30
Feedback for Drive 2
In
16
31
Logic Command Status for Drive 3
Out
16
32
Logic Status for Drive 3
In
16
33
Reference for Drive 3
Out
16
34
Feedback for Drive 3
In
16
35
Logic Command Status for Drive 4
Out
16
36
Logic Status for Drive 4
In
16
37
Reference for Drive 4
Out
16
38
Feedback for Drive 4
In
16
1
The size for this Register Object Instance is 32 bits per drive. For
example, if the module is operating in Multi-Drive mode, and is configured
with Drives 0 through 4, then the size is 160 bits.
2
The structure for this Register Object Instance is a Mask word followed by
a Command word for each drive. The Logic Command for each drive is
set to the value of the second word of the data where there are ones in
the first word of data. Logic Command = (Logic Command and not Mask
word) or (Command word and Mask word)
Instance
Description
Input/
Output
Size
(in bits)
Attribute
ID
Access
Rule
Name
Data
Type
Description
1
Get
Revision
UINT
1
2
Get
Max Instance
UINT
38
3
Get
Number of Instances
UINT
38
100
Set
Control Timeout
UINT