System Setup Chapter 1

DeviceNet Connections

DeviceNet versions of the PanelView terminal have a DeviceNet
communication port and an RS-232 port for file transfers/printing.
Connect the PanelView terminal to a DeviceNet link using DeviceNet
cable, catalog number 1485C-P1A50, -P1A150, -P1A300. The
illustration shows an SLC or PLC controller. Another option would be
a ControlLogix controller with a 1756-DNB module.

1747-SDN DeviceNet

Scanner Module

Cable

Catalog No. 2711-NC13,

2711-NC14, 2706-NC13

Cable 1485C-P1A50, -P1A150, -P1A300

1771-SDN DeviceNet
Scanner Module

Requires 24 Volt
Power Supply

PLC-5 Controller

PanelView 1000 Terminal

SLC 5/03, /04, /05 Controller

5

1

DeviceNet Port

RS-232 Port

Serial Link

PanelBuilder32 Software

DeviceNet
Terminal Block

Terminal

Signal

Function Color

1

COM

Common

Black

2

CAN_L

Signal Low

Blue

3

SHIELD

Shield

Uninsulated

4

CAN_H

Signal High

White

5

VDC+

Power Supply

Red

1

5