Publication 2711-QS003D-EN-P - June 2009

19

System Setup Chapter 1

Remote I/O Connections

Remote I/O versions of the PanelView terminal have both an RIO
adapter and an RS-232 file transfer/printer port. The RIO adapter lets
the terminal connect to any 1771 Remote I/O link. The PanelView
terminal connects to an RIO scanner using cable, catalog number
1770-CD, equivalent to Belden 9463.

Cable

2711-NC13, 2711-NC14, 2706-NC13

Node 2

PanelView 1000 RS-232

Terminal Shown

Node 0

Personal Computer

PanelBuilder32 Software

Node 1

PLC-5 Controller

RIO Port

1770-CD Cable

(Belden 9463)

RS-232 Port

Remote I/O Port

3-pin Terminal Block Connector

To RIO Port

Node 1

SLC Controller with

1747-SN Scanner Module

RIO Port

ControlLogix Controller

RIO Module (1756-DHRIO)

Important: Wire with clear insulation connects to
terminal #2 of the 3-pin Remote I/O connector.

82 or 150 Ohm

termination resistor

2 Clear
SH Shield
1 Blue

Clear 2

Shield SH

Blue 1

RIO Port

Serial Port

COM1 or COM2