PLC-5 Data Pass–Through
D–9
Publication 2706-6.2
1784-KT Interface Module Set Up Parameters
Use the following when setting up the Pass-Through function.
DH + Connection Type
Select: Direct if your programming computer and your PLC-5 are
the only devices on the DH+ link or if there are multiple
devices on the link and your programming computer is the
first or last (physical) device on the link.
Select: Multi-Drop if there are multiple devices on the link and your
programming computer is not first or last (physical) device
on link.
KT Address
The bit address that you assign to the 1784-KT Module using the
DIP switch on the module.
DH + Network Access
Select: Local if the PLC to which the DL40 is attached is on the
same DH+ link as your programming computer.
Select: Remote (Bridge) if the PLC to which the DL40 is attached is
on a separate DH+ link (connected by Data Highway) from
the DH+ link to which your programming computer is
attached.
If you are using remote DH+ networks, you must also supply:
Local Bridge Address
0 to 376 (octal)
The Data Highway address that you assign to the 1785-KA Module
connecting the DH+ link containing your programming computer to
Data Highway. This address must match the DIP switch settings on
the module.
Remote Bridge Address
0 to 376 (octal)
The Data Highway address that you assign to the 1785-KA Module
connecting the DH+ link containing your PLC-5 (to which the DL40
is attached) to Data Highway. This address must match the DIP
switch settings on the module.