beautypg.com

Setup information – Rockwell Automation 2706-LSW DL40 PLUS OFFLINE PROG.SFTWR.USER MANUAL User Manual

Page 140

background image

PLC-5 Data Pass–Through

D–8

Publication 2706-6.2

Refer to the following set up parameters, when setting up
communications files.

1784-KL Interface Module Set Up Parameters

Use the following when setting up the Pass-Through function.

DH + Connection Type

Select: Direct if your programming computer and your PLC-5 are

the only devices on the DH+ link or if there are multiple
devices on the link and your programming computer is the
first or last (physical) device on the link.

Select: Multi-Drop if there are multiple devices on the link and your

programming computer is not first or last (physical) device
on link.

DH + Network Access

Select: Local if the PLC to which the DL40 is attached is on the

same DH+ link as your programming computer.

Select: Remote (Bridge) if the PLC to which the DL40 is attached is

on a separate DH+ link (connected by Data Highway) from
the DH+ link to which your programming computer is
attached.

If you are using remote DH+ networks, you must also supply:

Local Bridge Address

0 to 376 (octal)

The Data Highway address that you assign to the 1785-KA Module
connecting your computer’s DH+ link to Data Highway. This
address must match the DIP switch settings on the KA Module.

Remote Bridge Address

0 to 376 (octal)

The Data Highway address that you assign to the 1785-KA Module
connecting your PLC-5’s DH+ link to Data Highway. This address
must match the DIP switch settings on the KA Module.

Setup Information