Chapter 7

Troubleshooting and Maintenance

7–2

If there is no display on the DTAM Plus, verify that the proper voltage is
present at the DTAM Plus power supply terminal block (check label on back
of unit). If no voltage is present, check the power to/from the power source.

The most common DTAM Plus problems are related to cabling
configurations and the communication parameters (baud rate, data bits,
parity). These parameters must be identical for both the DTAM Plus and the
controller. Cabling and the communications parameters are always the first
things to check.

If the communications cabling and communications parameters are correct,
perform the diagnostic tests (described in this chapter) to verify that the
DTAM Plus is functioning properly.

Refer to the following table when the DTAM Plus displays an error message.

Message

Probable Cause(s)

Corrective Action(s)

Checksum:failed

Read Only Memory (ROM) is incorrect.

Possible defective ROM. Reset the DTAM Plus and
re-check. If problem still exists, re-download the
operating system through the programming soft-
ware. If problem still exists, send DTAM Plus for
repair.

RAM fail

RAM memory failed write or read test.

Reset the DTAM Plus and re-check. If problem still
exists, send DTAM Plus for repair.

Check-sum: nnnn (CFG)
Check-sum: nnnn (DTAM Plus)
*.CFG File Invalid

Application file checksum is incorrect.

Possible bad application file. Download the applica-
tion (.CFG) file and re-check.

Watch Dog Fault
Push Key to Continue

Watch dog timer not within specs.

If problem persists, send DTAM Plus for repair.

Watch Dog Fault
Push Key to Reset

Watch dog timer timed out or pass bits not set.

If problem persists, send DTAM Plus for repair.

Allen-Bradley SLC 50X
Establishing Comm

Attempting to communicate with an SLC.

Normal display when initiating communications with
an SLC.

Allen-Bradley SLC 50X (or PLC-5)
Establishing Comm

Attempting to communicate with a PLC.

Normal display when initiating communications with
a PLC.

Allen-Bradley RIO
SCANNER NOT FOUND

No communications with Remote I/O link.

Check cabling and communications parameters
to verify that the controller matches those of the
DTAM Plus.

SLC not found

This display is displayed after a 2 second interval of
attempting to establish communications with the
SLC.

Communications not established with the SLC.
Check cabling and communications parameters
to verify that the SLC matches those of the DTAM
Plus.

PLC not found

This display is displayed after a 2 second interval of
attempting to establish communications with the
PLC.

Communications not established with the PLC.
Check cabling and communications parameters
to verify that the PLC matches those of the DTAM
Plus.

Communication Loss
Press ENTER to Reset

Communication with the SLC was lost after 16 retry
attempts.

Check DTAM Plus to controller cabling. Check SLC
operating conditions.

Common Operating Problems

Error Messages