Page 124: 11ć1, Troubleshooting

background image

Chapter

11

11-1

Troubleshooting

This chapter gives you an introduction to diagnosing and resolving any
problems you may have in operating an application involving the IBM PC
I/O Scanner. After reading this chapter you should be able to:

check the installation of the scanner and correct it if necessary

check your program for likely errors and correct them

check and correct the connections of your 1771 Series I/O modules and

adapters

determine whether any remaining problems are most likely in your

software, in the scanner, or in the attached adapters and modules.

You should also have the manuals for your 1771 Series I/O products handy.

A troubleshooting chart for the 6008–SI module is presented on the pages
that follow.

Problem:

Possible Solution:

Scanner does not

communicate with the IBM

U_D1 diagnostic program

does not run

Check dip switches 7-10 on the scanner board.

If IBM-XT, these switches should be open. If IBM-AT or T-50, these

switches should be closed.

(open = 1, closed = 0)

Check that dip switches 1-6 correspond to the address supplied in

the setup_6008() library routine or the /a option of the U_D1

program (open = 1, closed = 0)

Check memory map to insure a clear 6k + 1 memory window

Last resort. Set dip switches 1-6 to an open area of user RAM, or

remove some user RAM to create an open area. Install 6008-SI

there.

Chapter Objectives

Troubleshooting the I/O

Scanner