Rockwell Automation 6008-SI IBM PC I/O SCNNR 6008-SI User Manual
Page 120

Chapter 10
User Diagnostic Program
10-8
Autoconfigure
A
command: no data required.
Setup
SE
command: The program prompts for a one-digit baud rate multiplier (1
and 2 are valid), then for a one-digit resistor value (1 to connect the line
termination resistor and 0 to disconnect). Just pressing the
Enter
key in
response to either of the first two prompts leaves the previous value
unchanged.
There is a third prompt, for debugging mode: a 1 disables the scanner’s
watchdog and any other value (including just the
Enter
key) re-enables it.
Scan list
SC
command: The program prompts for the length of the scan list and then
the scan list itself. You enter each adapter in the scan list as a one-digit
rack number (0–7) followed immediately by a one-digit starting group
number (0, 2, 4, or 6).
You may need to make several identical responses in a row. You can
compress this repetitive input by using a repeat count with an asterisk. For
instance,
3*14
would enter the adapter at rack 1, group 4, in the next 3
positions in the scan list.
link statulFault dependent group
F
command: The program asks you for the rack and starting group number
of each adapter in the current scan list. You reply with the fault dependent
group number (0 to 7, or N for no group).
As with the scan list command, you may need to make repetitive
responses. Again, use a repeat count with an asterisk. For instance,
6*N
is
equivalent to making the
N
response 6 times, leaving the next 6 adapters
out of any fault group.