5-8 Module Diagnostics and Troubleshooting
Table 5.5 1769-OF4CI and -OF4VI Extended Error Codes
Error Type
Hex
Equivalent
(1)
Module
Error
Code
Extended Error
Information
Code
Error Description
Binary
Binary
No Error
X000
000
0 0000 0000
No Error
General Common
Hardware Error
X200
001
0 0000 0000
General hardware error; no additional information
X201
001
0 0000 0001
Power cycle reset state
X216
001
0 0001 0110
Microprocessor watchdog error
X220
001
0 0010 0000
Firmware corrupt (checksum failure)
X221
001
0 0010 0001
Firmware checksum error in NVRAM (calibration data checksum
failure)
Hardware-
Specific Error
X300
001
1 0000 0000
General hardware error (ASIC)
1769-OF4CI and
-OF4VI Specific
Configuration
Error
X401
010
0 0000 0001
Invalid input range selected (channel 0)
X402
010
0 0000 0010
Invalid input range selected (channel 1)
X403
010
0 0000 0011
Invalid input range selected (channel 2)
X404
010
0 0000 0100
Invalid input range selected (channel 3)
X409
010
0 0000 1001
Invalid data format selected (channel 0)
X40A
010
0 0000 1010
Invalid data format selected (channel 1)
X40B
010
0 0000 1011
Invalid data format selected (channel 2)
X40C
010
0 0000 1100
Invalid data format selected (channel 3)
X411
010
0 0001 0001
Invalid fault value (channel 0)
X412
010
0 0001 0010
Invalid fault value (channel 1)
X413
010
0 0001 0011
Invalid fault value (channel 2)
X414
010
0 0001 0100
Invalid fault value (channel 3)
X419
010
0 0001 1001
Invalid idle value (channel 0)
X41A
010
0 0001 1010
Invalid idle value (channel 1)
X41B
010
0 0001 1011
Invalid idle value (channel 2)
X41C
010
0 0001 1100
Invalid idle value (channel 3)
X421
010
0 0010 0001
Invalid clamps (channel 0)
X422
010
0 0010 0010
Invalid clamps (channel 1)
X423
010
0 0010 0011
Invalid clamps (channel 2)
X424
010
0 0010 0100
Invalid clamps (channel 3)
X429
010
0 0010 1001
Invalid ramp rate (channel 0)
X42A
010
0 0010 1010
Invalid ramp rate (channel 1)
X42B
010
0 0010 1011
Invalid ramp rate (channel 2)
X42C
010
0 0010 1100
Invalid ramp rate (channel 3)