1769-of4ci and -of4vi enable/disable channel, 1769-of4ci and -of4vi enable/disable channel -9 – Rockwell Automation 1769-OF4VI Compact I/O Isolated Analog Modules User Manual
Page 61
![background image](/manuals/579768/61/background.png)
Publication 1769-UM014B-EN-P - May 2010
Module Data, Status, and Channel Configuration for the Output Modules 4-9
1769-OF4CI and -OF4VI Enable/Disable Channel
This configuration selection (bit 15 of Configuration Word 0) allows each
channel to be individually enabled.
Table 4.7 1769-OF4CI and -OF4VI Output Channel Configuration Word 1
Define
Indicate
Bit Settings
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1769-OF4CI
Output
Range
Select
0…20 mA dc
0 0 0
4…20 mA dc
0 0 1
Output
Data
Select
Raw/Proportion
al Counts
0 0 0
Engineering
Units
0 0 1
Scaled for PID
0 1 0
Percent Range
0 1 1
1769-OF4VI
Output
Range
Select
-10…+10V dc
0 0 0
0…5V dc
0 0 1
0…10V dc
0 1 0
1…5V dc
0 1 1
Output
Data
Select
Raw/Proportion
al Counts
0 0 0
Engineering
Units
0 0 1
Scaled for PID
0 1 0
Percent Range
0 1 1
TIP
A channel that is not enabled has zero voltage or current at
its terminal.