Error codes, Error codes -6 – Rockwell Automation 1769-OF4VI Compact I/O Isolated Analog Modules User Manual
Page 78
Publication 1769-UM014B-EN-P - May 2010
5-6 Module Diagnostics and Troubleshooting
Configuration Errors
If you set the fields in the configuration file to invalid or unsupported values,
the module ignores the invalid configuration, generates a non-critical error,
and keeps operating with the previous configuration.
Each type of analog module has different features and different error codes.
See 1769-IF4I Extended Error Codes on page 5-6 and 1769-OF4CI and
-OF4VI Extended Error Codes on page 5-8.
Error Codes
Error codes can help troubleshoot your module.
Table 5.4 1769-IF4I Extended Error Codes
Error Type
Hex
Equivalent
(1)
Module
Error
Code
Extended Error
Information
Code
Error Description
Binary
Binary
No Error
X000
000
0 0000 0000
No Error
General Common
Hardware Error
X200
001
0 0000 0000
General hardware error; no additional information
X201
001
0 0000 0001
Power-up reset state
Hardware-
Specific Error
X300
001
0 1000 0000
General hardware error
X301
001
0 1000 0001
Microprocessor hardware error
X302
001
1 0000 0010
A/D converter communication error