beautypg.com

Error codes, Error codes -6 – Rockwell Automation 1769-OF4VI Compact I/O Isolated Analog Modules User Manual

Page 78

background image

Publication 1769-UM014B-EN-P - May 2010

5-6 Module Diagnostics and Troubleshooting

Configuration Errors

If you set the fields in the configuration file to invalid or unsupported values,
the module ignores the invalid configuration, generates a non-critical error,
and keeps operating with the previous configuration.

Each type of analog module has different features and different error codes.
See 1769-IF4I Extended Error Codes on page 5-6 and 1769-OF4CI and
-OF4VI Extended Error Codes on page 5-8.

Error Codes

Error codes can help troubleshoot your module.

Table 5.4 1769-IF4I Extended Error Codes

Error Type

Hex

Equivalent

(1)

Module

Error

Code

Extended Error

Information

Code

Error Description

Binary

Binary

No Error

X000

000

0 0000 0000

No Error

General Common

Hardware Error

X200

001

0 0000 0000

General hardware error; no additional information

X201

001

0 0000 0001

Power-up reset state

Hardware-

Specific Error

X300

001

0 1000 0000

General hardware error

X301

001

0 1000 0001

Microprocessor hardware error

X302

001

1 0000 0010

A/D converter communication error