Rockwell Automation 1788-CN2FFR EtherNet/IP and ControlNet to FOUNDATION Fieldbus Linking Device User Manual
Page 37
Rockwell Automation Publication 1788-UM057B-EN-P - September 2014
35
Set Up in the Studio 5000 Logix Designer Application
Chapter 2
Copy and Paste
After the device configuration is done, you can copy and paste the configuration
to speed up the configuration process.
Move
You can move a device in the live list to another field device index even if the
devices have been configured and are providing process variables.
Remove
A device configuration can also be removed (deleted).
Set H1 Node Address
Used to change the H1 node address on the field device. We recommend that you
set the node address from 17 through 247. The linking device uses 16, and node
addresses above 247 are placed in the visitor List.
Set H1 Physical Tag
Use to change the tag name that is stored in the field device.
Merge Online and Offline
The device merge option is used when you want to merge an online device with
the offline configuration of a certain device index. Use this option when
performing a device exchange for a faulty device.
Mapping Report
Produces a report that describes in detail the configuration of the field device.
Export Device and Import Device
A device configuration can be exported to a file which can later be imported
again. This option helps when you have multiple devices with the same
configuration.
IMPORTANT
If a configuration is stored in the linking device at the specific field device
index, it is also removed (deleted).