Chapter 4
C
Communicating with the Smart
Transmitter Interface
4-31
Word 09: HART hexadecimal flag assignment is 00 (low byte); most
significant byte of 24 bit device identification number is hexadecimal 00
(high byte).
Word 10: middle byte of 24 bit device identification number is
hexadecimal 15 (low byte); least significant byte is hexadecimal 11
(high byte). The 24 bit device ID is hexadecimal 001511.
Word 11: HART packet check byte received is hexadecimal 09 (low
byte); zero padding (high byte).
Table 4.P
Programmable Controller to Smart Transmitter Interface Ć BTW Data Long Frame
Format for HART Command 1
Octal Bits
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Decimal Bits
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word 00
Smart Transmitter Interface Channel Number
Smart Transmitter Interface Command
Word 01
Smart Transmitter Interface Parameter
Smart Transmitter Interface Control
Word 02
HART Address
HART Delimiter
Mas
Adr
0
Manufacturer
Identification Code
Lng
Frm
0
0
0
0
Frame Type
Word 03
Device ID
(Most Significant Byte)
Manufacturer's
Device Type
Word 04
Device ID
(Least Significant Byte)
Device ID
(Middle Byte)
Word 05
Byte Count
HART Command
Word 06
0
0
0
0
0
0
0
0
Check Byte
Table 4.Q
Example BTW Data Offset at D9:10 Ć Long Frame Format for HART Command 1
Address
0
1
2
3
4
5
6
D9:10
0110
0000
A682
000D
1115
0001
0000
Long Frame Word Contents Ć Programmable Controller to Smart
Transmitter Interface (Offset at D9:10)
Word 00: Smart Transmitter Interface Command is hexadecimal 10 (low
byte); Smart Transmitter Interface Channel is hexadecimal 01 (high
byte).