Communicating with the Smart
Transmitter Interface
Chapter 4
Communicating with the Smart Transmitter
Interface
4-18
Table 4.F
Smart Transmitter Interface Error Codes
Error Code
(hex)
Definition
Description
General Errors
00
No Error
The Smart Transmitter Interface processed the last received
command, and no errors were detected.
01
Downloading
Firmware
The Smart Transmitter Interface firmware is being upgraded
over the RSĆ232C port. The last received command cannot be
processed.
02
No Corresponding
BTW
The Smart Transmitter Interface received a BTR but does not
know what data is being requested. All BTRs must be
preceded by a BTW indicating what response to return in a
BTR.
03
Command Still in
Progress
The Smart Transmitter Interface is still obtaining the HART
Response from a field device and cannot respond with the
requested data. The programmable controller should reissue
the BTR request to obtain the response.
Command Errors
10
Invalid Command
The Smart Transmitter Interface command is invalid and
cannot be processed.
11
Invalid Channel
Number
The Smart Transmitter Interface channel number is invalid.
The command cannot be processed.
12
Invalid HART
Message
The HART packet encapsulated within a Smart Transmitter
Interface packet is invalid and cannot be forwarded to a field
device.
13
Invalid Channel
List
The channel list provided with the Enable Burst Monitor Mode
command contains an invalid entry or is incorrectly terminated.
The command cannot be processed.
14
Invalid Parameter
An invalid parameter is provided with the Smart Transmitter
Interface command and so it cannot be processed.
15
Invalid Control
An invalid control byte is included with the Smart transmitter
Interface command. The command cannot be processed.
16
Invalid DF1 Packet
Length
The length of the DF1 packet is not consistent with the length
specification in that packet. The command cannot be
processed.
Device Errors
20
Burst Mode Device
Not
Communicating
The Smart Transmitter Interface is not receiving burst data
from a field device in burst mode. Either Burst mode has been
turned off in the field device or it is too busy to send burst table
data. The error code is cleared once the Smart Transmitter
Interface receives new burst data from the device.
21
No Response
Received From
Device
The Smart Transmitter Interface has not received a response
from a field device after exhausting all retry attempts.
22
No Valid Burst
Data
The Smart Transmitter Interface does not have data in its
Burst Monitor Table for the requested channel. Either the
Smart Transmitter Interface was not commanded to monitor
the channel for burst data, or the field device is not in burst
mode.