Chapter

7

7-1

Troubleshooting

We describe how to troubleshoot your module by observing indicators and by
monitoring status bits reported to the processor.

At powerup, the module momentarily turns on both indicators as a lamp test,
then checks for

correct RAM operation
EPROM

operation

EEPROM

operation

a valid write block transfer with configuration data

Thereafter, the module lights the green RUN indicator when operating without
fault, or lights the red FAULT indicator when it detects fault conditions. If the
red FAULT indicator is on, block transfers will be inhibited.

The module also reports status and specific faults (if they occur) in every
transfer of data to the programmable controller processor. Monitor the green
and red indicators and status bits in word 1 of the BTR file when
troubleshooting your module.

Figure 7.1
Module Indicators

RUN

FLT

10528-I

ISOLATED

ANALOG INPUT

Green RUN Indicator

Red FLT (fault) Indicator

Chapter Objective

Diagnostics Reported by the
Module