Block transfer write format – Rockwell Automation 1771-IL/B , D17716.5.91 ISOLATED ANALOG INPUT Module User Manual
Page 27
Module Configuration
Chapter 4
4-3
Table 4.B
Input Voltage and Current Ranges for the Analog Input Module
Nominal Voltage
or Current Range
Default Scaling
BCD Output Range
Voltage or
Current Per Bit
Data from
A/D Converter
Voltage or
Current Per Bit
+1 to +5V
0000 to +4095
0.98mV
3063 to 15316
0.33mV
0 to 5V
0000 to +4095
1.22 mV
32768 to 15316
0.33mV
-5 to +5V
-4095 to +4095
1.22mV
-15316 to 15316
0.33mV
-10 to +10V
-4095 to +4095
2.44mV
-30632 to 30632
0.33mV
0 to +20mA
0000 to +4095
0.0049mA
0 to 15316
0.0013mA
+4 to +20mA
0000 to +4095
0.0039mA
3063 to 15316
0.0013mA
-20 to +20mA
-4095 to +4095
0.0049mA
-15316 to 15316
0.0013mA
Note: Voltage and current input ranges are selectable on a per channel basis.
To get the same resolution available from the A/D converter, scale each
channel as shown in Table 4.C.
Table 4.C
Scaling Endpoints
Voltage/Current
Range
Minimum
Scaling Endpoint
Maximum
Scaling Endpoint
+1 to 5V
3063
15316
4 to 20mA
3063
15316
0 to 5V
0
15316
0 to 20mA
0
15316
-5 to 5V
-15316
15316
-20 to 20mA
-15316
15316
-10 to 10V
-30632
30632
0 to 10V
-30632
30632
You select the format to enter values in the block transfer write table. Bit
08 (10 octal) of BTW word 2 sets the parameters for scaling, high and low
alarms, and the digital filter constant.
Decimal Bit 08
Octal Bit 10
BTW Data Format
You must enter all values in:
0
BCD (default)
BCD
1
Two’s Complement Binary
Two’s Complement Binary
Block Transfer Write Format