Block transfer write format – Rockwell Automation 1771-IL/B , D17716.5.91 ISOLATED ANALOG INPUT Module User Manual

Page 27

background image

Module Configuration

Chapter 4

4-3

Table 4.B
Input Voltage and Current Ranges for the Analog Input Module

Nominal Voltage

or Current Range

Default Scaling

BCD Output Range

Voltage or

Current Per Bit

Data from

A/D Converter

Voltage or

Current Per Bit

+1 to +5V

0000 to +4095

0.98mV

3063 to 15316

0.33mV

0 to 5V

0000 to +4095

1.22 mV

32768 to 15316

0.33mV

-5 to +5V

-4095 to +4095

1.22mV

-15316 to 15316

0.33mV

-10 to +10V

-4095 to +4095

2.44mV

-30632 to 30632

0.33mV

0 to +20mA

0000 to +4095

0.0049mA

0 to 15316

0.0013mA

+4 to +20mA

0000 to +4095

0.0039mA

3063 to 15316

0.0013mA

-20 to +20mA

-4095 to +4095

0.0049mA

-15316 to 15316

0.0013mA

Note: Voltage and current input ranges are selectable on a per channel basis.

To get the same resolution available from the A/D converter, scale each
channel as shown in Table 4.C.

Table 4.C
Scaling Endpoints

Voltage/Current

Range

Minimum

Scaling Endpoint

Maximum

Scaling Endpoint

+1 to 5V

3063

15316

4 to 20mA

3063

15316

0 to 5V

0

15316

0 to 20mA

0

15316

-5 to 5V

-15316

15316

-20 to 20mA

-15316

15316

-10 to 10V

-30632

30632

0 to 10V

-30632

30632

You select the format to enter values in the block transfer write table. Bit
08 (10 octal) of BTW word 2 sets the parameters for scaling, high and low
alarms, and the digital filter constant.

Decimal Bit 08

Octal Bit 10

BTW Data Format

You must enter all values in:

0

BCD (default)

BCD

1

Two’s Complement Binary

Two’s Complement Binary

Block Transfer Write Format