Module Configuration

Chapter 4

4-10

If a write block with all zeroes is written to the module, the default
selections will be:

1 to 5V dc or 4 to 20mA (depends on voltage/current selection jumper)
BCD data format
no real time sampling (RTS)
no digital filter
no

scaling

no

alarms

Note: Input data is set to 0 until an initial block transfer write is received
by the module.

Figure 4.4
Word Assignments for the Isolated Analog Input Module
(1771-IL series B)Block Transfer Write

Decimal Bits

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Octal Bits

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

1

Range Selection Bits for Channels 1 through 8

Word 1

8

7

6

5

4

3

2

1

2

Real Time Sampling

Data

Format

BTW

Format

Digital Filter

3

8

7

6

5

4

3

2

1

8

7

6

5

4

3

2

1

3

Sign bits, maximum scaling values

Sign bits, minimum scaling values

4

Channel 1 - minimum scaling

5

Channel 1 - maximum scaling

6

Channel 2 - minimum scaling

7

Channel 2 - maximum scaling

8

Channel 3 - minimum scaling

9

Channel 3 - maximum scaling

10

Channel 4 - minimum scaling

11

Channel 4 - maximum scaling

12

Channel 5 - minimum scaling

13

Channel 5 - maximum scaling

14

Channel 6 - minimum scaling

15

Channel 6 - maximum scaling

16

Channel 7 - minimum scaling

Default Configuration