Chapter

5

5-1

Module Status and Input Data

In this chapter you will read about:

reading data from your module
block transfer read data format

Block transfer read programming moves status and data from the input
module to the processor’s data table in one I/O scan (Figure 5.1). The
processor’s user program initiates the request to transfer data from the
input module to the processor.

Figure 5.1
Word Assignments for the Isolated Analog Input Module
(1771-IL series B) Block Transfer Read

Decimal Bits

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Octal Bits

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Word 1

Not used

A

HF

IA

IF

RTS

IS

OR

PU

Status word

2

Not used

8

7

6

5

4

3

2

1

Underrange bits - Channels 1-8

3

Not used

8

7

6

5

4

3

2

1

Overrange bits - Channels 1-8

4

Not used

8

7

6

5

4

3

2

1

Polarity bits - Channels 1-8

5

Channel 1 Input

Channel 1 Input

6

Channel 2 Input

Channel 2 Input

7

Channel 3 Input

Channel 3 Input

8

Channel 4 Input

Channel 4 Input

9

Channel 5 Input

Channel 5 Input

10

Channel 6 Input

Channel 6 Input

11

Channel 7 Input

Channel 7 Input

12

Channel 8 Input

Channel 8 Input

13

Not used

8

7

6

5

4

3

2

1

Low Alarm Bits

14

Not used

8

7

6

5

4

3

2

1

High Alarm Bits

15

8

7

6

5

4

3

2

1

CF

EF

Not used

S

G

O

Calibration Status Bits