Installing the Input Module

Chapter 2

2-7

When using shielded cable wire, ground the foil shield and drain wire only
at one end of the cable. We recommend that you wrap the foil shield and
drain wire together and connect them to a chassis mounting bolt
(Figure 2.4). At the opposite end of the cable, tape exposed shield and
drain wire with electrical tape to insulate it from electrical contact.

Figure 2.4
Cable Grounding

Remove a length of cable
jacket from the Belden 8761
cable.

Pull the foil shield and bare
drain wire from the insulated
wires.

Bare drain
wire

Insulated
wires

Foil
shield

Twist the foil shield and drain
wire together to form a single
strand.

Attach a ground lug.

20104

Belden 8761 Cable

19480

When you connect grounding conductors to the I/O chassis
grounding stud, place a star washer under the first lug, then
place a nut with captive lock washer on top of each ground lug.

Grounding Stud

1

Use the cup washer if crimp-on lugs are not used.

Chassis Ground

Single-point Grounding

Ground Lug

Nut

Ground Lug

1

Star
Washer

I/O Chassis Side Plate

Nut and Captive
Washer

External-tooth Washers

#10 Thread-forming screw

19923

Refer to Wiring and Grounding Guidelines, publication 1770-4.1, for additional information.

Grounding