beautypg.com

Rockwell Automation 1771-IL/B , D17716.5.91 ISOLATED ANALOG INPUT Module User Manual

Page 43

background image

Module Calibration

Chapter 6

6-3

4.

After the connections stabilize, request the offset calibration by setting bit
00 in block transfer write word 37 and sending a block transfer write
(BTW) to the module. Refer to Table 6.A.

When the BTW is sent, all channels are calibrated to 0.00000V.

Table 6.A
Write Block Transfer Word 28

Decimal Bit

15 14 13 12 11 10 09 08 07 06 05 04 03

02

01

00

Octal Bit

17 16 15 14 13 12 11 10 07 06 05 04 03

02

01

00

Inhibit Calibration

Requested Auto-Calibration

Word 37

8

7

6

5

4

3

2

1

Set these bits to 0

Requested

Save

Values

Requested

Gain Cal.

Requested

Offset Cal.

NOTE: Normally, all channels are calibrated simultaneously (decimal bits
08-15; octal bits 10-17 of word 37 are 0). To disable calibration on any
channel, set the corresponding bit 08 through 15 decimal, or 10 through
17 octal, of word 37.

5.

Queue block transfer reads (BTRs) to monitor for offset calibration
complete and any channels which may have not calibrated successfully.
Refer to Table 6.B.

Table 6.B
Read Block Transfer Word 13

Decimal Bit

15 14 13 12 11 10 09 08

07

06

05 04 03

02

01

00

Octal Bit

17 16 15 14 13 12 11 10

07

06

05 04 03

02

01

00

Uncalibrated Channels

Auto-Calibration Status

Word 13

8

7

6

5

4

3

2

1

Cal.

Fault

EEPROM

Fault

Not used

Save to

EEPROM
Complete

Gain Cal.

Complete

Offset

Cal.

Complete

6.

Reset bit 00 (0) (requested offset calibration).

7.

Proceed to Gain Calibration below.