beautypg.com

Advanced instruction set chapter 6 – Rockwell Automation 1772-LV Mini-PLC - 2/15 Programmable Controller (Series B) Programming and Operations User Manual

Page 62

background image

Advanced Instruction Set

Chapter 6

6Ć5

Rung 6: An input device is controlling the timer.

Table 6.A

Approximate Execution Time Per Scan

(in average microseconds)

Instruction

Name

Symbol

Instruction

True

Instruction

False

Examine on,Examine Off

Ć| |Ć,Ć|/|Ć

10

5

Output Energize

Ć( )Ć

19

19

Output Latch

Ć(L)Ć

19

15

Output Unlatch

Ć(U)Ć

19

15

Get

Ć[G]Ć

27

Ć

Put

Ć(PUT)Ć

22

15

Equal

Ć(=)Ć

22

5

Less Than

Ć(<)Ć

31

5

Get Byte

Ć|B|Ć

11

Ć

Limit Test

Ć|L|Ć

23

5

Counter Reset

Ć(CTR)Ć

23

15

Retentive Timer Reset

Ć(RTR)Ć

24

16

Timer OnĆdelay

Ć(TON)Ć

140

60

Retentive Timer OnĆdelay

Ć(RTO)Ć

140

48

Timer OffĆdelay

Ć(TOF)Ć

145

70

Up Counter

Ć(CTU)Ć

130

110

Down Counter

Ć(CTD)Ć

135

115

Add

Ć(+)Ć

48

15

Subtract

Ć(Ć)Ć

80

19