beautypg.com

5ć14 – Rockwell Automation 1772-LV Mini-PLC - 2/15 Programmable Controller (Series B) Programming and Operations User Manual

Page 51

background image

Fundamental Instruction Set

Chapter 5

5Ć14

Counter Reset Instruction

Symbol: -(CTR)-

Purpose: Resets the up counter or down counter instructions’ accumulated
value and status bits to 0.

Syntax: Programmed as an output instruction. The AC and PR values are
displayed.

Function: When the rung condition becomes:

True

Accumulated value of the specified counter is reset to 000.
Status bits (14, 15, 16, 17) are reset.

False

No action is taken.

Section D

Data Manipulation Instructions

In this section you will read how data is transferred or compared when it is
stored in the data table.

To transfer or to compare stored data located in the data table use the following
data manipulation instructions:

Get
Put
Less Than
Equal To
Get Byte
Limit Test

Get

Symbol -|G|-

Purpose: Accesses 16 bits of data from one word location in the data table. It
does not determine rung logic continuity.

Syntax: Programmed in the condition area of the ladder diagram rung
(Figure 5.5). It can be located at the beginning a rung or with one or more
conditions preceding it.

Function: Always accesses the word to which it is addressed. It displays a
decimal number beneath the instruction. The lower 12 bits (bits 0-13) of the
specified word contain the data.

Introduction

Transfer Instructions