1746-OB16
0.388
1.400
7.60
1746-OB16E
0.150
0.675
3.07
1746-OBP8
0.300
0.675
3.08
1746-OBP16
0.310
1.250
6.26
1746-OG16
0.033
0.900
1.50
1746-OV8
0.775
0.675
6.90
1746-OV16
0.388
1.400
7.60
1746-OVP16
0.310
1.250
6.26
1746-OW4
0.133
1.310
1.90
1746-OW8
0.138
2.590
3.70
1746-OW16
0.033
5.170
5.70
1746-OX8
0.825
2.590
8.60
Table B.7 Combination Input/Output Module Heat Dissipation
Catalog Numbers
Watts per Point
Minimum
Watts
Total Watts
1746-IO4
0.27 per input point
0.133 per output point
0.75
1.60
1746-IO8
0.27 per input point
0.133 per output point
1.38
3.00
1746-IO12
0.27 per input point
0.133 per output point
2.13
4.60
1746-IO12DC
0.20 per input point
0.133 per output point
1.84
3.90
Table B.8 Speciality Module Heat Dissipation
Catalog Numbers
Watts per Point
Minimum
Watts
Total Watts
1746-BAS
Not Applicable
3.750
3.800
1746-FIO4I
Not Applicable
3.760
3.800
1746-FIO4V
Not Applicable
3.040
3.100
1746-HS
Not Applicable
consult factory
1746-HSCE
Not Applicable
consult factory
1746-HSCE2
Not Applicable
consult factor
1746-HSTP1
Not Applicable
consult factory
1746-NI4
Not Applicable
2.170
2.200
1746-NIO4I
Not Applicable
3.760
3.800
Table B.6 Output Module Heat Dissipation