Rockwell Automation 1788-EN2PAR EtherNet/IP and ControlNet to PROFIBUS PA Linking Device User Manual User Manual
Page 47
Rockwell Automation Publication 1788-UM058B-EN-P - September 2014
47
Logix Assemblies
Chapter 3
ParameterFault
This bit is set if there is a fault in the parameterization of the field device.
ParameterReq
This bit is set if the device has not received its parameterization.
FreezeMode
This bit is set if you enable Freeze mode in the parameterization of the field
device and a global control is sent to freeze the device PVs.
SyncMode
This bit is set if you enable Sync mode in the parameterization of the field device
and a global control is sent to synchronize the device PVs.
WatchDog
This bit is set if the watchdog is enabled in the parameterization of the field
device.
PAIdent
This is the identity number of the specific field device.
PVReal1…PVReal8
If you set a process variable to be a Real format, the data is displayed in this
section.
PVStatus1…PVStatus8
If you set a process variable to have a Status, the status value for the each PV is
displayed in this section.
See the user manual of the field device for the definition
of the PV status. In general, the status definitions are as
follows:
•
Good = a value
≥ 0x80
•
Uncertain = a value from 0x40…0x7F
•
Bad = a value
< 0x40 (for example, 0…0x3F)
PVInt1…PVInt8
If you set a process variable to be a 1-byte to 4-byte format, the data is displayed in
this image.