Field device input image – Rockwell Automation 1788-EN2PAR EtherNet/IP and ControlNet to PROFIBUS PA Linking Device User Manual User Manual
Page 46
46
Rockwell Automation Publication 1788-UM058B-EN-P - September 2014
Chapter 3
Logix Assemblies
ModuleStatus
This word is currently reserved.
Connection Status
If a field device is online and running (exchanging cyclic data), then the field
device index bit in the connection status is set. If the device goes offline, the bit is
cleared.
Field Device Input Image
Each field device displays its PA diagnostics and all available PVs and their status
as shown in
Figure 10
.
Figure 10 - Field Device Input Image
PANode
The node number of the field device on the PA bus.
OnlineRunning
This bit is set when the device is online and exchanging cyclic data.
ConfigFault
This bit is set if there is a fault in the configuration of the field device.
ExtDiagAvail
This bit is set when the field device has extra extended diagnostics available. This
bit can be dynamic.