Configure pv with multiple formats – Rockwell Automation 1788-EN2PAR EtherNet/IP and ControlNet to PROFIBUS PA Linking Device User Manual User Manual
Page 33
Rockwell Automation Publication 1788-UM058B-EN-P - September 2014
33
Set Up in the Studio 5000 Logix Designer Application
Chapter 2
Configure PV with Multiple Formats
In some cases (for example, positioner field devices), there are multiple input and
output PVs per slot. See
Valve Positioner Configuration on page 34
for details.
To configure multiple PV formats for the slot, follow these steps.
1.
Select the Manual Config check box and click the Configure button to
open the Slot Configuration dialog box.
2.
Select the check boxes for the input and output PVs that you want to
configure.
3.
From the pull-down menu, choose the PV formats for the selected inputs
and outputs.
4.
Click Ok to save the PV formats.
IMPORTANT
Select the number of inputs and outputs, and their respective PV formats, as
shown in the user manual of the field device. In the input image of the field
device, the PV is set per the manual slot configuration.