Rockwell Automation 1608P-200A480V... HC-DySC User Manual User Manual
Page 34
34
Rockwell Automation Publication 1608P-UM005A-EN-P - November 2014
Chapter 6
Maintenance
Table 11 - System Event Table
Event
Code
Code Name
Full Name
Severity
Area
Event Description
Event Resolution
1
POWER_ON
DySC Power On
Informational
Unit
Power re-applied to the DySC.
No action needed.
4
T_FAN_ST
Fan Test Start
Informational
Unit
Start acknowledgment of DySC fan test.
No action needed.
5
T_IN_ST_1
Inverter Test (.5 cycles) Start
Informational
Unit
Start acknowledgment of DySC 0.5 cycle inverter test.
No action needed.
6
T_IN_ST_2
Inverter Test (3 cycles) Start
Informational
Unit
Start acknowledgment of DySC 3 cycle inverter test.
No action needed.
7
T_IN_ST_3
Inverter Test (5.5 seconds) Start
Informational
Unit
Start acknowledgment of DySC 5.5 second inverter test.
No action needed.
9
EXTERNAL
External Inhibit
Auto-Resetting
Inverter
Controller is inhibited by another phase controller.
Review event details from other phase controllers.
11
RUN_TO
Inverter Run Time out
Auto-Resetting
Inverter
DySC inverter had a total cumulative runtime of more than rated.
No action needed.
12
LIM_CYCLE
Inverter Limit Cycle Timeout
Auto-Resetting
Inverter
Power was re-applied more than once within a 58 second period.
No action needed.
13
STAT_OT
Static Switch Over-Temperature
User Attention
Static Switch
Static switch heatsink temperature was greater than maximum rating.
Verify ambient temperature is within DySC specification. Check
for damaged fans. Check for dirty or obstructed air filters.
14
OVERLOAD
Overload
User Attention
Unit
Inverter inhibited because load current exceeded maximum rating.
Reduce load. In parallel DySC systems, verify proper current
sharing among slave cabinets.
15
DC_OV
DC Bus Over-Voltage
User Attention
Inverter
Positive or negative half of DC bus voltage exceeded maximum rating.
Verify line voltage is within ratings. Verify proper DySC
application. Call service.
16
CNTRL_UV
Controller Power Under-Voltage
User Attention
Inverter
DySC control power supply is out of tolerance.
Verify DySC is online and line voltage is within ratings. Call
service.
17
OUTPUT_UV
Output Under-Voltage
User Attention
Inverter
DySC output voltage was less than 80% of nominal during sag correction.
Sag condition likely outside of DySC specification.
Verify line voltage is within ratings. Verify proper DySC
application.
18
INV_OC
Inverter Over-Current
User Attention
Inverter
Inverter current exceeded maximum rating during sag correction.
Verify load current is within ratings. Verify mechanical bypass
switch is open. Verify proper DySC application.
19
DC_UV
DC Bus Under-Voltage
User Attention
Inverter
DC bus voltage below operational range.
Verify line voltage is within ratings.
Call service.
20
OUTPUT_OV
Output Over-Voltage
Call Service
Inverter
DySC output voltage was greater than 115% of nominal during sag
correction.
Call service.
25
SYNC_ERR
Line Synchronization Error
Call Service
Inverter
Inverter not synchronized to line when sag detected.
Call service.
31
CONFIG
Configuration Alert
Call Service
Inverter
Controller configuration has changed.
Call service.
32
CNTRL_MEM
Controller Memory Busy
Auto-Resetting
Inverter
Controller is loading new data into Flash memory.
No action needed.
33
UNBALANCE
Start-Up Test: DC Bus Unbalance
Call Service
Inverter
Positive and negative halves of the DC bus did not charge equally during
power up.
Call service.
34
AC_V_CHK
Start-Up Test: AC Voltage Check
Call Service
Inverter
Output voltage was detected out of tolerance during the start-up test.
Call service.
35
ROLL_CALL
Start-Up Test: Controller Roll Call
Timeout
Call Service
Unit
Controller communication problem detected during start-up test.
Call service.