Chapter 5
Display Screen
System Events
The HC-DySC tracks all operational events which are classified into five groups
based on severity.
Table 7 - System Event Description
System Event Log
The “System Event Log” screen displays a list of the last 40 system events in
chronological order (See
Figure 23
). Reach this screen by pressing “SYSTEM
EVENTS” on the “HOME” screen.
Figure 23 - System Event Log
Table 8 - System Event Log Description
Description
Function
Informational
Purely informational. No action is required.
Auto-Resetting
The HC-DySC will reset within 60 seconds. No user action is required.
User Attention
User action may be required to correct a problem. The HC-DySC will reset 60
seconds after the error condition is corrected.
Manual-Reset
For system events that cause circuit breaker CBI to open a manual reset of the
DySC system will be required.
Call Service
For events classified as Call Service, factory trained service support will be
required. Contact Rockwell Automation technical support.
Description
Function
#
Unique ID (0-39) to identify the system event (unique within the list)
Time
Start time of the system event
Name
Short name of the system event.
Severity
Severity of the system event
Note: Use the up/down arrows to navigate through the list. Press the “SELECT” button to view additional detail about the system event.