Rockwell Automation Publication 1512A-UM100F-EN-P - May 2013

83

Appendix

C

ArcShield Chimney Installation Instructions

The following instructions are provided to ensure the proper installation and
function of chimney supplied with ArcShield enclosures. Refer to

Appendix A

for additional information related to ArcShield chimney before attempting to
follow these instructions.

Recommended Torque
Values

1 /4 -20 Thread Fasteners — 7.5 N•m (6 lb•ft)
5 /16 -18 Thread Fasteners — 14 N•m (11 lb•ft)

Figure 84 - Chimney Exhaust Label

IMPORTANT

Plan the location where the plenum will exhaust (refer to

Appendix A

). The

plenum exhaust area is to be marked as a Hazardous Zone, and labeled per

Figure 84

.

ARC FLASH HAZARD

PRESSURE RELIEF EXIT

AREAS TO BE:

- INACCESSIBLE TO PERSONNEL
WHILE EQUIPMENT ENERGIZED.
- FREE OF OBSTRUCTIONS
(REFER TO USER MANUAL).

SEVERE INJURY OR

DEATH MAY RESULT.

SORTIE DE L’ÉVENT

RÉGION ÊTRE:

- INACCESSIBLE AUX PERSONNEL
PENDANT QUE L’ÉQUIPEMENT
EST SOUS TENSION.
- DÉMUNI D’OBSTRUCTIONS
(RÉFÉRER AU MANUEL)

RISQUE DE BLESSURES

CORPORELLES GRAVES

OU MÊME LA MORT.

DANGER

DANGER

HAZARD D’ARC ÉLECTRIQUE