Chapter 5

Maintenance

Figure 56 - Isolation Switch Linkage Assembly Angle Location

5. Loosen the lock nuts at each clevis (Note: one is a left-handed thread).

6. Adjust the isolation switch mechanical threaded linkage with a wrench

until the overall travel angle of the switch link is within the required
tolerance.

7. Hold the position of the threaded linkage and tighten the lock nuts.

Figure 57 - Isolation Switch Mechanical Threaded Linkage

Must have
tolerance of
0/+6º

Shaft Assembly

Red Glass
Polyester
Switch Link

Isolation Switch
Mechanical
Threaded Linkage