background image

60

Rockwell Automation Publication 1512A-UM100F-EN-P - May 2013

Chapter 5

Maintenance

4. Insert a 6.35 mm (0.25 in.) diameter pin into the cam groove between the

cam follower and the end of the cam groove.

Figure 61 - Adjusting Auxiliary Contacts, left side view (ISa Auxiliary Contact Shown)

5. Adjust the cam on the shaft so that the gap from the cam follower to the

end of the cam groove is the width of the pin — 6.35 mm (0.25 in.).

6. Move the isolation switch handle to the OFF (open) position and check

that nothing prevents the cam from rotating with the shaft.

7. Tighten the bolt holding the cam to the shaft. Move the isolation switch

handle to the ON position and recheck the gap using the pin.

8. Verity that auxiliary contact ISa is open when the isolation switch is open.

Verify that ISa contact is closed when isolation switch is closed.

Adjusting the Normally Closed (ISb) Contacts

1. Move the isolation switch handle to the OFF (open) position.

2. Loosen the bolt holding the inside cam to the shaft. Do not loosen the bolt

entirely. The cam should not be able to rotate freely on the shaft.

3. Insert a 6.35 mm (0.25 in.) diameter pin into the cam groove between the

cam follower and the end of the cam groove.

4. Adjust the cam on the shaft so that the gap from the cam follower to the

end of the cam groove is the width of the pin — 6.35 mm (0.25 in.).

5. Tighten the bolt that holds the cam to the shaft. Move the isolation switch

handle to the OFF position and recheck the gap using the pin.

CA TA

LO

G NO

.

700-CPM

SER. A

20

AMP

Cam

Cam Follower

Auxiliary Contact

Gap: 0.25 in. (6.35 mm)