Advanced set up group (cont.) – Rockwell Automation 1305 AC Drive, Series A and B, Firmware 4.xx-5.xx User Manual

Page 94

background image

Chapter 5 – Programming

5-22

Advanced Set Up Group (cont.)

[Stop Select]

Parameter # 10

Factory Default ‘‘Ramp”

[Stop Select]

Parameter Type Read & Write

This parameter selects the stopping mode when the drive
re e ves v d s p

d

Units None

Settings ‘‘Coast”

Causes the Drive to Turn Off Immediately

This parameter selects the stopping mode when the drive
receives a valid stop command.

‘‘Ramp”

Drive Decelerates to 0 Hz, Then Turns Off – Requires
a Value In [Decel Time 1] or [Decel Time 2]

‘‘DC Brake”

Injects DC Braking Voltage Into the Motor – Requires a
Value in Both [Decel Hold Time] & [Decel Hold
Level].

‘‘S-Curve”

Drive ramps to stop using a fixed ‘‘S-Curve” profile.
Stop time is twice the selected decel time.

[DC Hold Time]

Parameter # 12

Factory Default 0 Sec

[DC Hold Time]

Parameter Type Read & Write

Minimum 0 Sec

This value sets the amount of time that the [DC Hold
Level]
voltage will be applied to the motor when the stop
mode is set to either ‘‘DC Brake” or ‘‘Ramp.” When in
‘‘Coast ” mode and the drive is stopped and restarted
within the [DC Hold Time] setting, the speed will resume
at the output frequency prior to the stop command.

Units 1 Second

Maximum 15 Sec

[DC Hold Time]

Figure 5.13 Ramp

Figure 5.14 DC Brake

Volts and Speed

y

Voltage

y

Stop Command

Stop Command

[DC Hold Time]

[DC Hold Level]

[DC Hold Level]

Time

Time

Speed

Speed

Voltage

Volts and Speed