[Analog Invert]
Parameter # 84
Factory Default ‘‘Disabled”
[Analog Invert]
Parameter Type Read & Write
This parameter enables the inverting function for the 0-10
Volt and 4-20mA analog input signal at TB2.
Units None
Settings ‘‘Enabled”
Maximum Input Commands [Minimum Freq]
Minimum Input Commands [Maximum Freq]
Volt and 4-20mA analog input signal at TB2.
‘‘Disabled”
Maximum Input Commands [Maximum Freq]
Minimum Input Commands [Minimum Freq]
Figure 5.12 Analog Invert
[Maximum Frequency]
'
0 V
4 mA
Drive Output
y
10 V
20 mA
y
[Minimum Frequency]
'
Disabled
Enabled
[4-20mA Loss Sel]
Parameter # 81
Factory Default ‘‘Stop/Fault”
[4-20mA Loss Sel]
Parameter Type Read & Write
This parameter selects the drives reaction to a loss of a
s
e
e
ve
re
en y So r e s
Units None
Settings ‘‘Stop/Fault”
Drive Stops and Issues ‘‘Hz Err Fault” (F29)
T s p r
e er se e s e dr ves re
ss
4-20mA signal when the active [Frequency Source] is
IMPO TA T: T e dr ve u pu
s
e
‘‘Hold/Alarm”
Drive Maintains Last Output Freq and sets an Alarm bit
4-20mA. IMPORTANT: The drive output contacts can be
used to issue an alarm signal by setting [Output 1 Config]
r O p
2 on
r
IMPO TA T:
ss
‘‘Max/Alarm”
Drive Outputs [Maximum Freq] and sets Alarm bit
used to issue an alarm signal by setting [Output 1 Config]
or [Output 2 Config] to “alarm”. IMPORTANT: Loss of
s
s de ed s s
r s
‘‘Pre1/Alarm”
Drive Outputs [Preset Freq 1] and sets an Alarm bit
signal is defined as a signal < 3.5 mA or a signal >
20.5 mA.
‘‘Min/Alarm”
Drive Outputs [Minimum Freq] and sets an Alarm bit