Chapter 5 – Programming
5-17
Advanced Set Up Group (cont.)
[Break Voltage]
Parameter # 50
Factory Default See Table
[Break Voltage]
Parameter Type Read & Write
Minimum 0 Volts
1/2
HP
3/4
HP
1
HP
2
HP
3
HP
5
HP
This parameter sets the voltage the drive will output at
[Break Frequency]. Combined with [Break Frequency],
s v ue de er
es e
s per H r
e ee
d
Units 1 Volt
Maximum 50% of
Max. Drive
ed
s
230V
25
Volts
30
Volts
28
Volts
25
Volts
22
Volts
N/A
this value determines the Volts-per-Hz ratio between 0 and
[Break Frequency]. IMPORTANT: [DC Boost Select]
must be set to ‘‘Break Point” to activate this parameter.
Rated Volts
460V
50
Volts
52
Volts
55
Volts
47
Volts
44
Volts
41
Volts
[Maximum Voltage]
Parameter # 20
Factory Default Max. Drive Rated Volts
[Maximum Voltage]
Parameter Type Read & Write
Minimum 25% of Max. Drive Rated Volts
This parameter sets the highest voltage the drive will
output.
Units 1 Volt
Maximum 100% of Max. Drive Rated Volts
[Base Voltage]
[Base Frequency]
Maximum
'
a [Maximum Voltage]
[Maximum Frequency]
b
y
Motor Rated
Maximum
0 –
0
Volt-
age
Frequency
b
[Break Voltage]
[Break Frequency]
Start Boost
'
y
Motor Rated
'
Figure 5.7 Custom Volts-per-Hz
Pattern
This pattern is active only when
[DC Boost Select] is set to
‘‘Break Point.”
The following guidelines should be followed when setting up
a custom Volts-per-Hz curve:
1.
[Base Voltage] must be greater than [Start Boost].
2.
If [DC Boost Select] is set to “Break Point” then:
[Base Voltage] must be greater than [Break Voltage] and
[Break Voltage] must be greater than [Start Boost].
IMPORTANT:[Maximum Voltage] does not have to be set greater than [Base Voltage], but the maximum drive output is limited
to [Maximum Voltage].