Chapter 5 – Programming
5-47
Masks
This group of parameters contains binary masks for all control functions except the stop command. The
masks control which adapters can issue control commands.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
“Adapter 1”
Adapter 3
Adapter 4
Adapter 5
Not Used
Adapter 2
Adapter 6
Mask
“TB2”
Each mask contains a bit for each adapter.
Individual bits can be set to ‘‘0” to lockout
control by an adapter or set to ‘‘1” to permit an
adapter to have control.
Adapter 1
“Adapter 2”
“Adapter 3”
“Adapter 4”
“Adapter 5”
“Adapter 6”
N/A
TB2
[Logic Mask]
Parameter # 92
Factory Default 01111111
[Logic Mask]
Parameter Type Read & Write
This parameter determines which adapters are allowed to
control the drive logic commands. Setting a bit to ‘‘0”
(deny control) disables all command functions except stop
and frequency reference. IMPORTANT: In order to remove
an adapter from the drive without causing a drive
communications fault, the corresponding bit for that
adapter must be set to zero. IMPORTANT: This parameter
has no effect on the frequency value being sent from TB2
or any of the adapters.
Units Byte
Settings 1
0
Permit Control
Deny Control
[Direction Mask]
Parameter # 94
Factory Default 01111111
[Direction Mask]
Parameter Type Read & Write
This parameter determines which adapters can issue
forward/reverse commands. IMPORTANT: Terminal Block
(TB2) will have control unless masked out.
Units Byte
Settings 1
0
Permit Control
Deny Control