Chapter 5 – Programming

5-47

Masks

This group of parameters contains binary masks for all control functions except the stop command. The
masks control which adapters can issue control commands.

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

“Adapter 1”

Adapter 3

Adapter 4
Adapter 5

Not Used

Adapter 2

Adapter 6

Mask

“TB2”

Each mask contains a bit for each adapter.
Individual bits can be set to ‘‘0” to lockout
control by an adapter or set to ‘‘1” to permit an
adapter to have control.

Adapter 1

“Adapter 2”

“Adapter 3”

“Adapter 4”
“Adapter 5”

“Adapter 6”

N/A

TB2

[Logic Mask]

Parameter # 92

Factory Default 01111111

[Logic Mask]

Parameter Type Read & Write

This parameter determines which adapters are allowed to
control the drive logic commands. Setting a bit to ‘‘0”
(deny control) disables all command functions except stop
and frequency reference. IMPORTANT: In order to remove
an adapter from the drive without causing a drive
communications fault, the corresponding bit for that
adapter must be set to zero. IMPORTANT: This parameter
has no effect on the frequency value being sent from TB2
or any of the adapters.

Units Byte

Settings 1

0

Permit Control

Deny Control

[Direction Mask]

Parameter # 94

Factory Default 01111111

[Direction Mask]

Parameter Type Read & Write

This parameter determines which adapters can issue
forward/reverse commands. IMPORTANT: Terminal Block
(TB2) will have control unless masked out.

Units Byte

Settings 1

0

Permit Control
Deny Control