Digital input signals -24, 24vdc and 120vac circuits -24, Control and signal wiring – Rockwell Automation 1336R REGEN LINE REG User Manual
Page 76: Digital input signals important: customer
3–24
Regenerative Brake Operation
Control and Signal Wiring
Digital Input Signals
Important: Customer
EXTERNAL FAULT
and
ENABLE
circuits must be
connected to J15 and at logic high for the 1336
REGEN Converter to operate.
1336 REGEN Converter digital inputs are designed for operation at
either 24VDC or 120VAC. Digital input signal circuits must be capa-
ble of operating with high = true logic. For 24VDC operation,
+24VDC is available from the 1336 REGEN Converter Control
Board. For 120VAC operation, a separate 120VAC user supply is
required.
24VDC and 120VAC Circuits
!
ATTENTION: Ensure that all jumpers on the 1336
REGEN Converter Control Board are set correctly prior
to applying AC power to the board. Applying 120VAC to
the digital inputs when jumpers J10, J11 or J18 are set to
24VDC will permanently damage the Converter Control
Board.
IN THE LOW STATE . . .
MUST GENERATE A VOLTAGE
OF NO MORE THAN . . .
AND LEAKAGE CURRENT MUST
BE LESS THAN . . .
24VDC Circuits
8VDC
1.5mA Into a 2.5k
Ω
Load
120VAC Circuits
30VAC
10mA Into a 6.5k
Ω
Load
IN THE HIGH STATE . . .
MUST GENERATE A VOLTAGE
OF . . .
AND SOURCE CURRENT MUST
BE AT LEAST . . .
24VDC Circuits
20-26VDC
10mA
120VAC Circuits
81-132VAC
20mA
EXTERNAL RESET (DIGITAL IN)
COMM (DIGITAL COMMON)
ENABLE (DIGITAL IN)
– (24V DC COMM)
+ (24V
DC SUPPLY)
5
EXTERNAL FAULT (DIGITAL IN)
6
J15
4
3
2
1
+24V
DC (HIGH)
J11 120V
24V
Set Jumper J11 for 24V DC ENABLE Circuit Operation
J18 120V
24V
Set Jumper J18 for 24V DC EXTERNAL FAULT Operation
J10 120V
24V
Set Jumper J10 for 24V DC EXTERNAL RESET Circuit Operation
➊ Maximum wire length is 3.05 meters (10feet) — Use only for local control.
➊
➊
➊
➊
24V
DC Operation
Contacts are Shown in the Unpowered State
(or in the Powered State with no Enable or External Fault present)
EXTERNAL RESET (DIGITAL IN)
COMM (DIGITAL COMMON)
ENABLE (DIGITAL IN)
NOT USED
NOT USED
5
120V
AC RTN
4
3
2
1
120V
AC (HIGH)
120V
AC Operation
Contacts are Shown in the Unpowered State
(or in the Powered State with no Enable or External Fault present)
EXTERNAL FAULT (DIGITAL IN)
6
J11 120V
24V
Set Jumper J11 for 120V AC ENABLE Circuit Operation
J18 120V
24V
J10 120V
24V
Set Jumper J10 for 120V AC EXTERNAL RESET Circuit Operation
J15