Regenerative Brake Operation

Control and Signal Wiring

Digital Input Signals

Important: Customer

EXTERNAL FAULT

and

ENABLE

circuits must be

connected to J15 and at logic high for the 1336
REGEN Converter to operate.

1336 REGEN Converter digital inputs are designed for operation at
either 24VDC or 120VAC. Digital input signal circuits must be capa-
ble of operating with high = true logic. For 24VDC operation,
+24VDC is available from the 1336 REGEN Converter Control
Board. For 120VAC operation, a separate 120VAC user supply is
required.

24VDC and 120VAC Circuits

!

ATTENTION: Ensure that all jumpers on the 1336
REGEN Converter Control Board are set correctly prior
to applying AC power to the board. Applying 120VAC to
the digital inputs when jumpers J10, J11 or J18 are set to
24VDC will permanently damage the Converter Control
Board.

IN THE LOW STATE . . .

MUST GENERATE A VOLTAGE
OF NO MORE THAN . . .

AND LEAKAGE CURRENT MUST
BE LESS THAN . . .

24VDC Circuits

8VDC

1.5mA Into a 2.5k

Load

120VAC Circuits

30VAC

10mA Into a 6.5k

Load

IN THE HIGH STATE . . .

MUST GENERATE A VOLTAGE
OF . . .

AND SOURCE CURRENT MUST
BE AT LEAST . . .

24VDC Circuits

20-26VDC

10mA

120VAC Circuits

81-132VAC

20mA

EXTERNAL RESET (DIGITAL IN)

COMM (DIGITAL COMMON)

ENABLE (DIGITAL IN)

(24V DC COMM)

+ (24V

DC SUPPLY)

5

EXTERNAL FAULT (DIGITAL IN)

6

J15

4

3

2

1

+24V

DC (HIGH)

J11 120V

24V

Set Jumper J11 for 24V DC ENABLE Circuit Operation

J18 120V

24V

Set Jumper J18 for 24V DC EXTERNAL FAULT Operation

J10 120V

24V

Set Jumper J10 for 24V DC EXTERNAL RESET Circuit Operation

➊ Maximum wire length is 3.05 meters (10feet) — Use only for local control.

24V

DC Operation

Contacts are Shown in the Unpowered State
(or in the Powered State with no Enable or External Fault present)

EXTERNAL RESET (DIGITAL IN)

COMM (DIGITAL COMMON)

ENABLE (DIGITAL IN)

NOT USED

NOT USED

5

120V

AC RTN

4

3

2

1

120V

AC (HIGH)

120V

AC Operation

Contacts are Shown in the Unpowered State
(or in the Powered State with no Enable or External Fault present)

EXTERNAL FAULT (DIGITAL IN)

6

J11 120V

24V

Set Jumper J11 for 120V AC ENABLE Circuit Operation

J18 120V

24V

J10 120V

24V

Set Jumper J10 for 120V AC EXTERNAL RESET Circuit Operation

J15