Regenerative DC Bus Supply Operation

2–7

380-480VAC Power
Wiring

Figure 2.4 — 380-480VAC Power Line Filter Connections

Figure 2.5 — 380-480VAC 1321 10% Line Reactor Connections

LINE FILTER

PRECHARGE UNIT

LINE REACTOR

CONVERTER

Input Term. Output Term. Input Term. Output Term. Input Term. Output Term. Input Term.

R

IN

R

OUT

R

R1

R1

R2

R2

S

IN

S

OUT

S

S1

S1

S2

S2

T

IN

T

OUT

T

T1

T1

T2

T2

R

IN

PE — GND

(EARTH GROUND)

S

IN

T

IN

R

OUT

S

OUT

T

OUT

L

R

L

T

L

S

PE

(EARTH GROUND)

PE

(EARTH GROUND)

R

2

S

2

S

2

T

2

T

1

T

1

S

1

S

1

R

1

R

1

T

2

AC POWER IN

(FROM PRECHARGE UNIT)

AC POWER OUT

(TO CONVERTER)

R

2

1321 10% Line Reactor

380-480VAC Power Connections

380-480VAC input and output power
connections are made as shown in
Figure 2.4 through Figure 2.8.

!

ATTENTION: 1336
REGEN equipment will not
be properly synchronized
unless correct Filter-to-
Precharge-to-Line Reactor-
to-Converter AC power
connections are maintained.
Failure to maintain correct
phase-related connections
will result in equipment
malfunction and/or failure.