Programming – Rockwell Automation 1336R REGEN LINE REG User Manual
Page 48
2–32
Regenerative DC Bus Supply Operation
Programming
Parameter No.
16
Display Units
%
Parameter Type
Read/Write
Factory Default
130% DC
BASE
➊
Min/Max Value
120/135% DC
BASE
➊
Drive Units
100 = 4096
DC Bus Overvoltage Trip Level
This parameter sets the software over voltage trip point of the DC bus. The 1336 REGEN
Converter is factory set to prevent it from operating when DC bus voltage is 30% above
DC
BASE
volts.
➊
For 380VAC input Line Regeneration Packages, DC
BASE
volts = 537V.
For 460VAC input Line Regeneration Packages, DC
BASE
volts = 650V.
Parameter No.
17
Display Units
%
Parameter Type
Read/Write
Factory Default
60% DC
BASE
➊
Min/Max Value
50/100% DC
BASE
➊
Drive Units
100 = 4096
DC Bus Undervoltage Trip Level
This parameter sets the software under voltage trip point of the DC bus. The 1336 REGEN
Converter is factory set to prevent it from operating when DC bus voltage is less than 60% of
DC
BASE
volts.
➊
For 380VAC input Line Regeneration Packages, DC
BASE
volts = 537V.
For 460VAC input Line Regeneration Packages, DC
BASE
volts = 650V.
Parameter No.
18
Display Units
%
Parameter Type
Read/Write
Factory Default
115% AC
BASE
➊
Min/Max Value
110/130% AC
BASE
➊
Drive Units
100 = 4096
AC Line Overvoltage Trip Level 1 (Not Enabled)
This parameter sets a software over voltage trip point that is active when the 1336 REGEN
Converter is not enabled. The 1336 REGEN Converter is factory set to prevent it from being
enabled when the input AC line voltage is 15% above the AC
BASE
volts.
➊
For 380VAC input Line Regeneration Packages, AC
BASE
volts = 380V.
For 460VAC input Line Regeneration Packages, AC
BASE
volts = 460V.
Important: The 1336 REGEN Converter cannot be enabled for the [LOV Trip 1] to be
changed.
Parameter No.
19
Display Units
%
Parameter Type
Read/Write
Factory Default
130% AC
BASE
➊
Min/Max Value
120/135% AC
BASE
➊
Drive Units
100 = 4096
AC Line Overvoltage Trip Level 2 (Enabled)
This parameter sets a second software over voltage trip point that is active when the 1336
REGEN Converter is enabled. The 1336 REGEN Converter is factory set to trip if the input AC
line voltage is 30% above the AC
BASE
volts.
➊
For 380VAC input Line Regeneration Packages, AC
BASE
volts = 380V.
For 460VAC input Line Regeneration Packages, AC
BASE
volts = 460V.
Important: The 1336 REGEN Converter cannot be enabled for the [LOV Trip 2] to be
changed.