beautypg.com

Programming – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 48

background image

2–32

Regenerative DC Bus Supply Operation

Programming

Parameter No.

16

Display Units

%

Parameter Type

Read/Write

Factory Default

130% DC

BASE

Min/Max Value

120/135% DC

BASE

Drive Units

100 = 4096

DC Bus Overvoltage Trip Level

This parameter sets the software over voltage trip point of the DC bus. The 1336 REGEN
Converter is factory set to prevent it from operating when DC bus voltage is 30% above
DC

BASE

volts.

For 380VAC input Line Regeneration Packages, DC

BASE

volts = 537V.

For 460VAC input Line Regeneration Packages, DC

BASE

volts = 650V.

Parameter No.

17

Display Units

%

Parameter Type

Read/Write

Factory Default

60% DC

BASE

Min/Max Value

50/100% DC

BASE

Drive Units

100 = 4096

DC Bus Undervoltage Trip Level

This parameter sets the software under voltage trip point of the DC bus. The 1336 REGEN
Converter is factory set to prevent it from operating when DC bus voltage is less than 60% of
DC

BASE

volts.

For 380VAC input Line Regeneration Packages, DC

BASE

volts = 537V.

For 460VAC input Line Regeneration Packages, DC

BASE

volts = 650V.

Parameter No.

18

Display Units

%

Parameter Type

Read/Write

Factory Default

115% AC

BASE

Min/Max Value

110/130% AC

BASE

Drive Units

100 = 4096

AC Line Overvoltage Trip Level 1 (Not Enabled)

This parameter sets a software over voltage trip point that is active when the 1336 REGEN
Converter is not enabled. The 1336 REGEN Converter is factory set to prevent it from being
enabled when the input AC line voltage is 15% above the AC

BASE

volts.

For 380VAC input Line Regeneration Packages, AC

BASE

volts = 380V.

For 460VAC input Line Regeneration Packages, AC

BASE

volts = 460V.

Important: The 1336 REGEN Converter cannot be enabled for the [LOV Trip 1] to be

changed.

Parameter No.

19

Display Units

%

Parameter Type

Read/Write

Factory Default

130% AC

BASE

Min/Max Value

120/135% AC

BASE

Drive Units

100 = 4096

AC Line Overvoltage Trip Level 2 (Enabled)

This parameter sets a second software over voltage trip point that is active when the 1336
REGEN Converter is enabled. The 1336 REGEN Converter is factory set to trip if the input AC
line voltage is 30% above the AC

BASE

volts.

For 380VAC input Line Regeneration Packages, AC

BASE

volts = 380V.

For 460VAC input Line Regeneration Packages, AC

BASE

volts = 460V.

Important: The 1336 REGEN Converter cannot be enabled for the [LOV Trip 2] to be

changed.

T r i p

W

O V S

B

0 %

1 6

3

1

T r i p

W

U V S

B

0 %

1 7

6

i p 1

r

O V T

L

5 %

1 8

1

1

i p 2

r

O V T

L

0 %

1 9

3

1