Regenerative DC Bus Supply Operation

Programming

Overview

The 1336 REGEN Line Regeneration Package is designed so that
factory default parameter settings allow it to operate satisfactorily
under a wide variety of load and utility conditions.

Important: The 1336 REGEN Package has been shipped from the

factory with Parameter 1 set to the Regenerative Brake
Mode of operation. For Regenerative DC Bus Supply
applications, this parameter must be reset as described in
“Operational Mode” on page 2-29.

With the exception of Parameter 1, for the majority of applications
there should be no need to adjust parameters. Should utility or load
conditions deviate from the “normal” conditions listed in the
Specifications, the following parameters have been provided to allow
adjustments to factory settings.

Conventions

• Only parameters that are used in the Regenerative DC Bus Supply mode of

operation are listed in this chapter.

• Some parameters can be modified when the 1336 REGEN converter is

enabled. Other parameters can be modified only when the 1336 REGEN is
not enabled.

• Parameter Names appear in the display in the left column. If mentioned

in text, they will be shown in

[brackets]

.

• The

Parameter No.

is a unique number assigned to each of the 1336

REGEN Package parameters.

• The

Display Units

are units shown on the HIM — Bits, Amps, Volts,

Percentages or Numbers.

• The

Parameter Type

heading indicates whether or not the parameter is

read/write or read only. If read/write, whether or not it can be changed
while the converter is enabled.

• The

Factory Default

value is the value set at the factory. In most

circumstances this value should be sufficient for the application.

• The

Min/Max Value

is the lowest/highest setting for the parameter.

Drive Units

are internal units used to scale values properly when reading

or writing to the converter.