Brake fault contact monitoring, Brake fuses, Brake module jumper settings – Rockwell Automation 1336_F_E_T_S SERIES A CHOPPER BRAKE MODULE User Manual
Page 27: Wb110 have input voltage jumpers
Heavy Duty Dynamic Braking
27
1336-5.65 — March, 2007
Brake Fault Contact Monitoring
For all brake module ratings a fault contact has been provided to provide a
remote output signal. Should a brake fuse fail or the brake thermostat trip,
the brake fault contact will open. Interconnection wiring for remote brake
monitoring is provided in the Wiring Schemes section.
Brake Fuses
All brake modules are internally fused to protect brake components. When
replacing brake fuses, use only the type and size specified below.
Brake Module Jumper Settings
For the Mounting Requirements shown previously as well as the Wiring Schemes,
there can be only one master brake module to control dynamic braking. When
multiple brake modules are used, only one brake module can serve as the master
brake to control the remaining slave brake modules.
Dynamic Brake Fuse
Fuse Type
Rating
WA018
WB009
WC009
F1
&
F2
F1
&
F2
F1
&
F2
Ferraz Shawmut
A60Q or Equivalent
A60Q or Equivalent
A60Q or Equivalent
30A, 600V
15A, 600V
15A, 600V
WA070
WB035
WC035
F1
&
F2
F1
&
F2
F1
&
F2
Ferraz Shawmut
A70QS or Equivalent
A70QS or Equivalent
A70QS or Equivalent
125A, 700V
60A, 700V
60A, 700V
WA115
WB110
WC085
F1
&
F2
F1
&
F2
F1
&
F2
Ferraz Shawmut
A70QS or Equivalent
A70QS or Equivalent
A70QS or Equivalent
200A, 700V
200A, 700V
200A, 700V
BRAKE MODE
SLAVE MASTER
1
(2)
(3)
W1
Slave/Master Jumper Set to Master
BRAKE MODE
MASTER SLAVE
1 (2)(3)
W1
BRAKE MODE
SLAVE MASTER
(2)(1)
(3)
W1
Cat. No.
WA018
WB009
WC009
Cat. No.
WA070
WB035
WC035
Cat. No.
WA115
WB110
WC085
BRAKE MODE
SLAVE MASTER
W1
1
(2)
(3)
BRAKE MODE
SLAVE MASTER
(2)(1)
(3)
W1
Slave/Master Jumper Set to Slave
BRAKE MODE
MASTER SLAVE
1 (2)(3)
W1
Cat. No.
WA018
WB009
WC009
Cat. No.
WA070
WB035
WC035
Cat. No.
WA115
WB110
WC085
Input Voltage Jumper Set to 460V
VOLTAGE SELECT
380V 460V
1
(2)
(3)
W2
VOLT SELECT
380V 460V
(2)(1)
(3)
W2
Cat. No.
WB009
Cat. No.
WB035
WB110
Master Brake Module
Jumper Settings
For the master brake module,
leave slave/master jumper W1
factory set to master (jumper
positions 1
&
2).
Slave Brake Module
Jumper Settings
For each slave module, reset
jumper W1 to slave (jumper
positions 2
&
3).
Input Voltage Jumper Settings
Set jumper W2 on 460V models to
correspond to the nominal drive input
voltage. Setting the jumper between
positions 1
&
2 will select an input voltage of
415/460 volts. Setting the jumper between
positions 2
&
3 will select an input voltage of
380 volts.
Only models WB009, WB035
&
WB110 have input voltage jumpers.