Parameter 65 ċ command frequency, Parameter 66 ċ output frequency, Parameter 67ċ output pulses – Rockwell Automation 1336VT AC DRIVE 5-300AMP (2-160KW) PROGRAMMING MANUAL User Manual
Page 62: Parameter 68 ċ serial password, Parameter 69 ċ reverse status

Serial Port Parameters
Firmware Version 1.01-3.01
Chapter 4
4-12
Parameter 65 Ċ Command Frequency
Read Only
Units
Hertz
Min Value
0.00
Max Value
250.00
This parameter represents the present drive command frequency set by the
current command source. The current command source will be indicated by
a code from 0-9 and shown by selecting Parameters 5 or 6.
Parameter 66 Ċ Output Frequency
Read Only
Units
Hertz
Min Value
0.00
Max Value
250.00
This parameter represents and will display the actual output frequency of
the drive and will change as programmed parameters interact with the
Command Frequency, Parameter 65. It is used in the PLC Controller
Discrete Transfer.
Parameter 67Ċ Output Pulses
Read Only
Units
1 Rev/256
Min Value
0
Max Value
65535/256
This parameter represents the angular position of the output waveform to 1
in 256 parts of an output cycle. It will continually increment from 0 to
65535 or 65535 to 0, then repeat as long as the drive is running.
Parameter 68 Ċ Serial Password
Read and Write
Units
Code
Min Value
0
Max Value
9999
Factory Setting
0
This parameter stores the access code used with the remote handheld
programming device and is not intended to be used with remote I/O board
programming. Once set, you can read the password only through RIO
board programming.
Parameter 69 Ċ Reverse Status
Read and Write
Units
Code
Min Value
0
Max Value
1
Factory Setting
0