Local Parameter Programming
. . . . . . . . . . . . . . . . . . . . .
At all Programming and Display Panels, parameters 0Ć50 and 70Ć89
may be viewed (Read) while the drive is running. Eight of these
parameters display realĆtime events (such as present drive speed
and output current) that cannot be changed (Written to). The
remaining parameters may be changed as long as the drive isn't
running. A decimal point displayed in the far right corner indicates
that programming has been selected and that the enter button has
been pressed. Parameter values may be changed when the decimal
point is present. With the exception of Parameter 45 (which is
programmable in 0.01 kHz increments), all Programming and Display
Panels allow all frequency parameters to be programmed in 0.1 Hertz
increments and all time parameters to be programmed in 1 second
increments.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Four pushbuttons on all Programming and Display Panels are used
for both viewing and programming parameters.
. . . . . . . . . . . .
The PR pushbutton is used to switch from the operating display to the
parameter viewing display. Once in the viewing display, the PR
pushbutton is used to increment through the parameters.
. . . . .
The Enter pushbutton is used to switch from viewing to programming
but only when Parameter 0 is displayed, and only if switch SW1 is
set to allow parameter programming. When programming parameters,
the Enter pushbutton is also used to store the displayed value.
.
These buttons are only functional in the programming mode. When
programming parameters, the increment and decrement pushbuttons
are used to scroll up or down to the parameter value to be entered.
Pressing both buttons simultaneously will end programming and
return the drive to the operating display.
. . . . . . . . . . . . . . . . .
After exiting the programming mode, the stop command must be
cycled to reset the drive and confirm that programming is complete.
Failure to follow these instructions will result in an F11 (Operator Error)
fault.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SW1 is a rocker switch only accessible on the chassis mounted Local
Programming and Display Panel. The switch can be accessed only
with the drive cover removed and may be used to disable the Enter
pushbutton and control access to local programming.
. . . . . . . .