Parameter 46 ċ pulse scale factor, Parameter 47 -- language – Rockwell Automation 1336VT AC DRIVE 5-300AMP (2-160KW) PROGRAMMING MANUAL User Manual
Page 48

Local and Serial Port Parameters
Firmware Version 1.01-3.01
Chapter 3
3-34
Parameter 46 Ċ Pulse Scale
Factor
Freq
P
R
P
R
Enter
Ratio
1
255
64
Read and Write
Units
Minimum Value
Maximum Value
Factory Setting
This parameter establishes the input pulse ratio required to produce a
proportional output command frequency when the pulse train input is
selected. The command frequency is determined by dividing the pulse train
frequency by the value set by Parameter 46. For example, at 64, a pulse
train input of 3,840 Hz produces a drive command frequency of 3,840
÷
64
or 60 Hz.
Maximum pulse input frequency = 250(Hz) x 255(Scale) = 63750 pulses
per second.
Important: The following use the drive pulse train input to control the
drive output frequency and require that Parameter 46 be set to 64:
•
1336-MOD-G1 — The BCD Interface Board
•
1336-MOD-N1 — The Isolated Signal Conditioner Board
Parameter 47 -- Language
Freq
P
R
P
R
Enter
Code
0
5
0
Read and Write
Units
Minimum Value
Maximum Value
Factory Setting
1336-MOD-E1, the Handheld Terminal, has the ability to display text in
one of six languages. The setting of this parameter determines which
language will be displayed.
•
0 = English
•
1 = French
•
2 = Spanish
•
3 = Italian
•
4 = German
•
5 = Japanese