Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 4

4-8

Parameter 59 Ċ Drive Status

Read Only

Units

Byte

Min Value

0

Max Value

255

This parameter is an eight-bit word that corresponds to the status byte read
by the PLC Controller input image table. It reports the actual operating
status of the drive.

BIT 0 — Direction

0 = forward

1 = reverse

BIT 1 — Enable

0 = drive (not) enabled

1 = drive enabled

BIT 2 — Fault

0 = fault not present

1 = drive faulted

BIT 3 — Alarm

0 = alarm not present

1 = one of six alarms is present

BIT 4 — Run

0 = drive stopped

1 = drive running

BIT 5 — Set Speed

0 = drive not at Frequency Command,

Parameter 65

1 = drive is within Frequency

Command limits, Parameter 65

BIT 6 — Accel

0 = drive is not accelerating

1 = drive is accelerating

BIT 7 — Decel

0 = drive is not decelerating

1 = drive is decelerating