Parameter 26 ċ preset/2, Accel, Cont.) – Rockwell Automation 1336VT AC DRIVE 5-300AMP (2-160KW) PROGRAMMING MANUAL User Manual
Page 34

Local and Serial Port Parameters
Firmware Version 1.01-3.01
Chapter 3
3-20
Parameter 26 Ċ Preset/2
nd
Accel
If Parameter 26 is set to 1, SW1, SW2, Speed Select and Parameter 72 will
(cont.)
control the selection of Run, Accel and Decel as follows:
Run at Frequency Select 1, Parameter 5
Speed
Parameter
Accel at:
SW1
SW2
Select
72
Decel at:
False
False
False
Off
Accel Time 1, Parameter 7
Decel Time 1, Parameter 8
True
False
False
Off
Accel Time 2, Parameter 30
Decel Time 1, Parameter 8
False
True
False
Off
Accel Time 1, Parameter 7
Decel Time 2, Parameter 31
True
True
False
Off
Accel Time 2, Parameter 30
Decel Time 2, Parameter 31
Run at Frequency Select 2, Parameter 6
Speed
Parameter
Accel at:
SW1
SW2
Select
72
Decel at:
False
False
True
Off
Accel Time 1, Parameter 7
Decel Time 1, Parameter 8
True
False
True
Off
Accel Time 2, Parameter 30
Decel Time 1, Parameter 8
False
True
True
Off
Accel Time 1, Parameter 7
Decel Time 2, Parameter 31
True
True
True
Off
Accel Time 2, Parameter 30
Decel Time 2, Parameter 31
Run at Frequency Select 1, Parameter 5
Speed
Parameter
Accel at:
SW1
SW2
Select
72
Decel at:
False
False
False
On
Accel Time 1, Parameter 7
Decel Time 1, Parameter 8
True
False
False
On
Accel Time 2, Parameter 30
Decel Time 1, Parameter 8
False
True
False
On
Accel Time 1, Parameter 7
Decel Time 2, Parameter 31
True
True
False
On
Accel Time 2, Parameter 30
Decel Time 2, Parameter 31
Run at Preset Frequency 4, Parameter 73
Speed
Parameter
Accel at:
SW1
SW2
Select
72
Decel at:
False
False
True
On
Accel Time 1, Parameter 7
Decel Time 1, Parameter 8
True
False
True
On
Accel Time 2, Parameter 30
Decel Time 1, Parameter 8
False
True
True
On
Accel Time 1, Parameter 7
Decel Time 2, Parameter 31
True
True
True
On
Accel Time 2, Parameter 30
Decel Time 2, Parameter 31