Serial Port Parameters
Firmware Version 1.01-3.01
Chapter 4
4-5
Parameter 57 Ċ Serial Mask
Read and Write
Units
Byte
Min Value
0
Max Value
255
Factory Setting
0
This parameter permits the masking of any one of the bits defined in
Parameter 56. Each bit in this parameter must be set to 1 to allow the
corresponding bit in Parameter 56 to be fully functional.
Important: If power is removed from the drive, a default state will occur
resetting all bits in Parameter 57 to 0.
BIT 0 — Decel Time
— 0 = use SW2 at terminal block TB3 to
select Decel Time 1 or 2. Bit 0 of
Parameter 56 ignored.
1 = use bit 0 of Parameter 56 to select
Decel Time 1 or 2. SW2
at
terminal block TB3
i
gnored.
BIT 1 — Accel Time
— 0 = use SW1 at terminal block TB3 to
select Accel Time 1 or 2. Bit 1 of
Parameter 56 ignored.
1 = use bit 1 of Parameter 56 to select
Accel Time 1 or 2. SW2 at
terminal block TB3 ignored.
BIT 2 — Frequency Control
— 0 = use SW2 at terminal block TB3 to
select Preset Frequency 1-7. Bit 2
of Parameter 56 ignored.
1 = use bit 2 of Parameter 56 to select
Preset Frequency 1-7. SW2 at
terminal block TB3 ignored.
BIT 3 — Frequency Control
— 0 = use SW1 at terminal block TB3 to
select Preset Frequency 1-7. Bit 3
of Parameter 56 ignored.
1 = use bit 3 of Parameter 56 to select
Preset Frequency 1-7. SW1 at
terminal block TB3 ignored.