Protection Functions

3-9

865-UM001A-EN-P – July 2009

Figure 3.7 – Block Diagram of the Differential Overcurrent Stage ΔI>


The stage ΔI> can be configured to operate as shown in Figure 3.8.
This dual slope characteristic allows more differential current at
higher currents before tripping.


Figure 3.8 – Example of differential overcurrent characteristics