Operating measures, Control functions – Rockwell Automation 865 Differential Protection Relay User Manual
Page 28
2-16
Local Panel User Interface
865-UM001A-EN-P – July 2009
Operating Measures
Control Functions
The default display of the local panel is a single-line diagram
including relay identification, Local/Remote indication, Auto-reclose
on/off selection and selected analogue measurement values.
Please note that the operator password must be active in order to be
able to control the objects. Please refer to ‘Opening Access’ on
page 2-15.
Toggling
Local/Remote
Control
1. Push the ENTER key. The previously activated object starts to
blink.
2. Select the Local/Remote object (“L” or “R” squared) by using
the arrow keys.
3. Push the ENTER key. The L/R dialog opens. Select “REMOTE”
to enable remote control and disable local control. Select
“LOCAL” to enable local control and disable remote control.
4. Confirm the setting by pushing the ENTER key. The
Local/Remote state will change.
Object
Control
1. Push the ENTER key. The previously activated object starts to
blink.
2. Select the object to control by using the arrow keys. Please note
that only controllable objects can be selected.
3. Push the ENTER key. A control dialog opens.
4. Select the “Open” or “Close” command by using the UP and
DOWN arrow keys.
5. Confirm the operation by pushing the ENTER key. The state of
the object changes.
Toggling Virtual Inputs
1. Push the ENTER key. The previously activated object starts to
blink.
2. Select the virtual input object (empty or black square)
3. The dialog opens
4. Select “VIon” to activate the virtual input or select “VIoff” to
deactivate the virtual input